170 Sizing ad Selection of Frequency Converters Sometimes motor manufacturers specify higher available torque at a lower duty cycle. A design optimised for intermittent operation can be economical, but it requires a more complex design as shown in Fig. 9.4 Obtaining a good match in speed selection. 120 % Torque 100 80 60 40 20 0 0 10 20 30 40 50 60 70 Hz Fig. 9.4 Obtaining a good match in speed selection 9.5 Derating of FC Maximum ambient temperatures are defi ned for FC’s, as for all electronic units. If the maximum ambient temperature is exceeded, it could lead to failure of the FC, but it also reduces the life-time of the electronics.

According to Arrhenius’ law, the life- time of an electronic component is reduced by 50% for each 10°C that it is operated above its specifi ed temperature. If FC’s have to be operated continuously near the maximum rated operating temperature and the specifi ed life-time of the FC still must be maintained, one option is to derate the power. Load 110% 100% 80% 60% 0% 20% 0% 0 2 4 6 8 10 12 14 16 kHz Fig. 9.5 Power reduction diagram for switching frequency and temperature Forced n load Quadratic load Forced ventilatio n Constant Constant load 20 - 6 0 Hz Hz Constant l oad 5 - 70 Hz