169 Sizing ad Selection of Frequency Converters 9.4 Control Range The advantage of a FC lies in its ability to regulate smoothly the speed of the motor. However, a wide variety of limits are set for the available controlling range. On the one hand the possible controlling range (speed range) depends on the control algorithms available of the unit. With the simple U/f control, control ranges that can vary within 1:15 can usually be achieved. If a control algorithm with a voltage vector control is used, a range of 1:100 is possible. If the actual motor speed is fed back to the FC by an encoder, adjustment ranges from 1:1,000 to 1:10,000 can be realised.
In addition to the limits of the control algorithms used, the fi eld-weakening range around the rated frequency of the motor and also low speed running must be taken into account. At low speeds, the motor’s self-cooling capacity is reduced. Therefore, in the event of continuous operation in this speed range, either a separately powered external fan must be used to cool the motor or the shaft load must be reduced. The speed below which the torque must be reduced can be found in the manufacturer’s data sheets.
If the motor is operated in the fi eld-weakening range, the reduction in the available torque with 1/f and the breakdown torque with 1/f 2 must also to be taken into account The fi eld-weakening range begins when the FC can no longer hold the U/f ratio constant. In Europe this point typically lies at 400 V/50 Hz and in North America at 460 V / 60 Hz. Torque [T] T B T L T S Constant excess load 160 % T N Break away torque Constant excess load 110 % Load torque n Fig. 9.3 Frequency converter with an optimised characteristic for quadratic loads and an over-load of 110%.
In order to achieve higher breakaway torque, the drive is sometimes started with a constant torque before the quadratic characteristic is used