168 Sizing ad Selection of Frequency Converters Table 9.2 Typical overloads in variable torque applications Even with quadratic load and an over-load capacity of 10% modern FC’s can be set up to have a higher break-away torque at start to ensure the proper start of the application. Remember to consider whether the application will always require a quadratic torque. For example, a mixer has a quadratic torque requirement when it is used to mix a very fl uid medium, but if the medium becomes highly viscous during processing, the torque requirement changes to constant.
9.3.1 Energy Effi ciency Concerns In chapter 4 Saving Energy with Frequency Converters we have seen diff erent considerations to be taken to save energy. It is important to remember, that the most energy effi cient solution is where the machine, the motor and the FC are selected for the best system effi ciency. For example fans speed will typically diff er from nominal speed, and so the motor, but many motors have their highest effi ciency at a speed between 75 and 100% of nominal speed. Some brands of FC have a built-in software function, which secure the best motor shaft power related to the FC input power.
Application Excess load Fan 110% Well pump 110% Booster pump / centrifugal pump 110% Filter infeed pump 110% Groundwater pump 110% Hot water pump 110% Non-clogging pump (solid materials) 110% Centrifugal pump / fan 110% Primary and secondary heating pump 110% Primary and secondary cooling water pump 110% Rainwater basin evacuation pump 110% Recycling sludge pump 110% Spiral pump (thin sludge) 110% Submerged motor pump 110% Excess sludge pump 110%