167 Sizing ad Selection of Frequency Converters Table 9.1 Typical overloads in constant torque applications With a constant load, an over-load reserve of approximately 50 to 60% for 60 seconds is typically used. If the maximum over-load limit is reached, the response depends on the FC used. Some types switch off their output and lose control of the load. Others are able to control the motor at the maximum over-load limit until they trip for thermal reasons. A quadratic load characteristic usually occurs in applications where increasing speed leads to an increasing quadratic load torque. Fans and centrifugal pumps are amongst the types of equipment that display behaviour of this kind.
Furthermore, most applications with a quadratic torque characteristic, such as centrifugal pumps or fans, do not require rapid acceleration phases. For this reason excess load reserves of 10 % are usually chosen for quadratic torques. See next page with examples of a quadratic load torque characteristic.
Application Excess load Lifting equipment 160% Conveyor belt 160% Stirrer / Mixer / centrifuge 160% Rotary piston compressor / piston compressor 150% Spiral pump (thick sludge) 150% Sludge dehydration press 150% Piston pump 150% Rotary gate valve 150% Rotary piston blower 110% Surface aerator 110% Metering pump 110% Booster pumps (2-stage) 110% Recirculation pump 110% Side channel blower for pool aeration 110%