veda — Facts Manual

166 Sizing ad Selection of Frequency Converters Fig 9.2 Identifi cation data of a Danfoss frequency converter The nameplate in Fig. 9.2 Identifi cation data of a Danfoss frequency converter comes from a 0.75 kW FC. The specifi ed current values apply to two diff erent voltage ranges. The FC can deliver 2.4 A with a mains voltage of 380 – 440 V. If the unit is supplied with a mains voltage of 441 – 500 V, it can deliver 2.1 A. However, the apparent power available with both voltage ranges is always 1.70 kVA. 9.3 Overload Capacity When selecting a FC, the load conditions of the application should always be taken into account fi rst.

A fundamental distinction is made between quadratic and constant load characteristics, which are the most common in practice. When a FC controls a motor, torque limits can be set for that motor. Selecting a FC with an apparent power rating that matches the rated current or power of the motor ensures that the required load can be driven reliably. However, an additional reserve is necessary in order to enable smooth acceleration of the load and also cater for occasional peak loads. Below are examples of a constant load torque characteristic. If a load is placed on a conveyor belt, the torque that must be applied to transport the load is constant over the entire speed range.