165 Sizing ad Selection of Frequency Converters 9.2 Rating of the Frequency Converter from Motor Specifi cations A widely used method for selecting FC’s is simply based on the rated power of the motor to be used. Although manufacturers specify the power ratings of their FC’s, this data normally relates to standard four-pole motors. Since the rated currents of motors diff er signifi cantly at the same power depending on the construction of the motor (e.g. standard motor and geared motor) and its number of pole pairs, this method is only suitable for providing a rough estimate of the proper FC size. Fig.
9.1 – Nominal current for 1.50kW motors of diff erent poles and manufacturer – shows examples of the rated currents of various 1.5 kW motors. 5.0 4.5 4.0 3.5 3.0 2.5 5.0 1.5 1.0 0.5 0.0 680 700 930 930 1410 1425 1440 2850 2900 680 700 930 930 RPM [min -1 ] 1410 1425 1440 2850 2900 Fig. 9.1 Nominal current for 1.50kW motors of diff erent poles and manufacturer Furthermore, it should be noted that the current drawn by a motor depends on whether it is connected in star or delta confi guration. For this reason FC’s should be selected based on the rated current for the type of confi guration selected (star or delta).
In addition to the motor current, the required motor voltage must be taken into account. Many FC’s can operate over a wide mains supply voltage range (e.g. 3 x 380 – 500V ) and thus provide a wide output voltage range. However, the apparent power that the unit can supply is constant over the whole voltage range. Thus the maximum output current is higher at a lower mains voltage and, correspondingly, lower at a higher voltage.