veda — Facts Manual

173 Sizing ad Selection of Frequency Converters Fig. 9.7 Total motor cable length is the sum of all connected parts 9.8 Environment Several considerations to the environment should be taken before installing a FC. The following factors should be checked: • Ambient temperature • Altitude • Environment • EMC • Harmonic distortion Minimum and maximum ambient temperature limits are specifi ed for all FC’s. Avoiding extreme ambient temperatures prolongs the life of the equipment and maximises overall system reliability. If the FC is installed in environment where the ambient temperature is higher than specifi ed, derating of the power is needed, see Derating of FC.

The cooling capability of air is decreased at lower air pressure. Above 1000 m derating of FC’s should be considered. Electronic equipment is sensitive to the environment. For instance moisture, dust and temperature can all infl uence the reliability of electronics. Reduced reliability causes downtime in the application with reduced productivity as a result. Therefore it is important to choose the right solution for the actual application. Basically, it is important to protect the electronics from a harsh environment. The best way to do that is to avoid the harsh environment by placing the electronics outside the harsh environment.

In most cases you cannot directly see how critical the environment is. It depends mainly on 4 factors, the concentration of pollutants present, dirt, the relative humidity