177 Sizing ad Selection of Frequency Converters to centralised systems. The potential for savings in the installation arise from reduced cable lengths and from using equipment modules that have already been built and tested by the machine manufacturer or supplier. 9.10 Examples The following examples illustrate the basic procedure for selecting a FC in the design process. Here the data sheet reproduced below is used for the selection process. The VLT® AutomationDrive FC 302 is selected as a FC that can operate with a 150m shielded cable.
Table 9.3 Data for the VLT® AutomationDrive P11K P15K P18K P22K HO NO HO NO HO NO HO NO Output Current Continuous (380-440 V) [A] 24 32 32 37.5 37.5 44 44 61 Intermittent (380-440V) [A] 38.4 35.2 51.2 41.3 60 48.4 70.4 67.1 Continuous (441-500 V) [A] 21 27 27 34 34 40 40 52 Intermittent (441-500 V) [A] 33.6 29.7 43.2 37.4 54.4 44 64 57.2 Output Power Continuous (400 V) [KVA] 16.6 22.2 26 30.5 42.3 Continuous (460 V) [KVA] 21.5 27.1 31.9 41.4 Typical shaft output [kW] 11 15 18.5 22.0 30.0 Max.
Input Current Continuous (380-440 V) [A] 22 29 34 40 55 Intermittent (380-440V) [A] 35.2 31.9 46.4 37.4 54.4 44 64 60.5 Continuous (441-500 V) [A] 19 25 31 36 47 Intermittent (441-500 V) [A] 30.4 27.5 40 34.1 49.6 39.6 57.6 51.7 Estimated power loss at rated max. load [W] 291 392 379 465 444 525 547 739 Ef ficiency 0.98 Max. cable size (mm²) ([AWG2]) 16 (6) 35 (2) Max. pre-fuses [A] 63 80