89 Frequency Converters and Motors 3.4.3. Acceleration and Deceleration Ramps (Ramp Up and Down) For many applications there are various reasons why the speed must not change too quickly but instead must be changed slowly or with smooth transitions. All modern FC’s have ramp functions to facilitate this. These ramps are adjustable and ensure that the speed reference is able to increase or decrease only at a preset rate. The acceleration ramp (ramp up) indicates how quickly the speed is increased. It is stated in the form of an acceleration time t acc and indicates how quickly the motor should reach the new speed. These ramps are mostly based on the rated motor frequency, e.g.

an acceleration ramp of 5 seconds means that the FC will take 5 seconds to go from standstill to the rated motor frequency (f n = 50 Hz). However there are some manufacturers who relate the acceleration and deceleration to the values between the minimum and maximum frequency. Fig. 3.8 Acceleration and deceleration times The deceleration ramp (ramp down) indicates how quickly the speed is decreased. It is stated in the form of a deceleration time t dec and indicates how quickly the motor should reach the new reduced speed. It is possible to go directly from acceleration to deceleration, since the motor always follows the output frequency of the inverter.

Ramp times can be set to such low values that in some situations the motor cannot follow the preset speed. This leads to an increase in the motor current until the current limit is reached. In the case of short ramp-down times, the voltage in the intermediate circuit may increase to such a level that the protective circuit will stop the FC. If the inertia of the motor shaft and the referred inertia of the load are known, the optimum acceleration and deceleration times can be calculated.