90 Frequency Converters and Motors t acc = J = n 2 –n 1 (T acc – T fric ) = 9.55 t dec = J = n 2 –n 1 (T acc + T fric ) = 9.55 J is the moment of inertia of the motor shaft and load [kgm2]. T fric is the friction torque of the system [Nm]. T acc is the overshoot torque used for acceleration [s]. T dec is the braking torque that occurs when speed reference is reduced [s]. n 1 and n 2 are the speeds at frequencies f 1 and f 2 [min -1 ]. If the FC allows an overload torque for a brief time, the acceleration and deceleration torques are set to the rated motor torque T. In practice, the acceleration and deceleration times are normally identical.
Example A machine has the following specifi cations: J = 0.042 kgm2 n 1 = 500 min -1 n 2 = 1000 min -1 T fric = 0.05 T N T N = 27 Nm Theoretical acceleration time can be calculated as follows: t acc = J = n 2 –n 1 (T acc – T fric ) = 9.55 0.042 = (1000–500) (27.0 – (0.05 = 27.0)) = 9.55 The ramp functions ensure that there is no abrupt change of speed, provided the FC is set to the calculated acceleration. This is essential for many applications like: • Ensuring bottles do not topple over on bottle transporting conveyors • Preventing water hammer in pump systems • Comfort in escalators or lifts Most often linear ramps are used.
However diff erent characteristics are possible for diff erent applications, for example, an “S” or “S 2 ” ramp. With the “S” ramp, the transitions to and from standstill are particularly gentle.