91 Frequency Converters and Motors F max Frequency a) Without smoothing b) With smoothing Fig. 3.9 Linear ramp a) and S-ramp (b) 3.4.4 Motor Torque Control Motor torque is another parameter which is important for the application, as shown in Fig. 3.5 The motor current can overshoot the current limit briefl y. Torque is the basis for the rotation or movement of a load. Reasons for controlling the torque include: • Limiting the torque to prevent damage on machine etc. • Control the torque to make more motors share the load. If an application is suddenly overloaded, and the FC is sized for overload, the machine can work for a given time in the overload mode.
However this excessive torque can be fatal for the machine or reduce the lifetime. Therefore, many FC’s can be programmed to send a warning in case of overload, but also limit the torque under specifi c conditions. As described in section 3.1 Basic Principles there is a relationship between current and torque. This relationship is not direct, but depends on slip, cos phi and temperature in the motor. The limitation based on measuring the current is not accurate. If the FC is the Space Vector type or the fl ux type (see chapter 2 Frequency Converters) the current is measured vectorially in all three motor phases, and the distribution of the current components is easy.
With this information the FC can calculate the torque precisely enough to make sure the machine is protected. In situations where more motors are on a common mechanical system, it is essential that the motors share the load equally. If the slip compensation factor is reduced, the motors will automatically balance their torque, but not necessarily maintain the desired speed. Accel. T 1 Run Decel. T 2 Accel. T 1 Run Decel. T 2