Electrical equipment 6.4 Design and protection of equipment Assessment of the maximum admissible cable length according to voltage drop Figure 6-42 Maximum cable length for a voltage drop of maximum 5 % If cable lengths in excess of 199 m are required, the cross-sectional area shall be increased to 16 mmІ (see table below). Source: DIN VDE0100, Supplement 5, Table 4:
Excerpt from the table "Admissible lengths of cables and cords for a specific voltage drop for copper conductors, values for four-core cables and cords 0.6/1kV"; highlighting by author with reference to example above Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 151