HiPhi — 6.4.1.6 Practical example

Electrical equipment 6.4 Design and protection of equipment Assessment of smallest possible short-circuit with SIMARIS design When the smallest possible short-circuit occurs, it shall be ensured in the machine that the upstream protective device trips within 5 seconds (see Chapter Initial symmetrical short- circuit current (Page 127) in the section "Smallest possible short-circuit".) This means that the residual current shall be at least sufficiently high to ensure that the short-circuit release responds. In the example described above, we use the Siemens SIMARIS design software to check whether this is the case. Assumption:

The cable length of the protective device to the load is 20 m Figure 6-43 Assessment of the smallest possible short-circuit (excerpt from SIMARIS design) The I kmin at the load is 2380 A. According to the data sheet, the short-circuit release of the selected 3RV2021-4EA10 motor starter protector responds at 400 A or higher (± 20 % tolerance) (see Chapter Selection of control devices (Page 135)). → The configuration is therefore correct. Control Panels compliant with IEC Standards and European Directives 152 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002