Control engineering - definition of terms and fundamental principles 5.14 Trip classes Normal and heavy-duty starting The graphic below illustrates the tripping times in relation to the tripping current with 3-pole loading from the cold state. CLASS 5 and CLASS 10 are often referred to as normal starting. Siemens provides combinations for CLASS 20, CLASS 30 and CLASS 40 for applications where a higher starting current is required for a prolonged period. These trip classes are also referred to as "heavy-duty starting". Source: Configuring the SIRIUS modular system, configuration manual, 09/2017 Figure 5-11 Example:
Tripping characteristics Control Panels compliant with IEC Standards and European Directives 68 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002