HiPhi — 5.15 Comparison of electrical characteristics

Control engineering - definition of terms and fundamental principles 5.15 Comparison of electrical characteristics 5.15 Comparison of electrical characteristics Plant – fuses/switching devices Table 5- 5 Comparing characteristics from the plant to characteristics of the fuse/switching device The fuse values (incl. tolerances) have to exceed the system values. Plant – circuit breaker Table 5- 6 Comparing characteristics from the plant to characteristics of circuit breakers The values of the breaker (incl. tolerances) shall be higher than the values from the plant.

Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 69 Characteristic Comments Plant Fuse Switching device Ik"max Rated breaking capacity Rated conditional short-circuit current R.m.s. value - rated conditional short-circuit current With respect to switching device, may depend on the type of application (load switching or merely isolation of equipment from supply). Ik"min Characteristic Unnecessary Calculated at the end of the cable or directly upstream of the next protective device. The fuse shall also be capable of interrupting this short-circuit current within 5 seconds.

îP Unnecessary Rated short- circuit making capacity Reference value for mechanical connections. Should be verified for switching devices (max. let-through value for fuses) S2k2 Operating I2tA Unnecessary The fuse requires the operating I2tA to ensure that the short-circuit current can be safely interrupted (pre-arcing energy + arcing energy). S2k2 conditional îP The short-circuit current through the fuse is limited to this value. It is necessary for the purposes of selectivity evaluation and can be used to dimension the downstream cables and devices. Characteristic Comments Plant Circuit breakers Ik"max ICU; ICS Determines the number of possible short-circuit interrupts.

Ik"min II; Id Current through the circuit breaker. When current selectivity is implemented, the setting value of the breaker (tolerance) should be lower than the plant value. Ik"min + time ICW Required for time-selectivity tasks. Determines the time period for which the circuit breaker can conduct the relevant short-circuit current. îP Icm Reference value for mechanical loading of the breaker and connections. This value determines the max. possible locking force of the breaker. S2k2 I2t; îD Let-through current of the circuit breaker. Applies particularly to current-limiting circuit breakers.