Control engineering - definition of terms and fundamental principles 5.17 Classes 5.17 Classes Classes define measures that are designed to protect against electric shock. The classes for electrical equipment are specified in EN 61140 (in VDE 0140-1 for Germany). Classes Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 71 Class Meaning 0 No special protection against electric shock is provided apart from basic insulation. Equipment in this class cannot be connected to the protective bonding circuit. Shock protection shall be afforded by the installation environment of the equipment.

Class 0 does not have a symbol or marking. It is planned to exclude class 0 from future releases of the international standard. Sale of equipment in class 0 is prohibited in some countries, e.g. in Germany and Austria. I Protective conductor All electrically conductive parts of the equipment enclosure (chassis) are connected to the protective bonding circuit of the permanent electrical installation that is at ground potential. Mobile devices in class I have a plug-and-socket connection with protective conductor contact.

The connection to the protective conductor is designed such that the protective conductor is the first to be connected or last to be disconnected when the plug is inserted in or pulled out of the socket outlet. The entry point of the connecting cable into the device shall be equipped with a strain- relief mechanism; when the cable is ripped out, the protective conductor shall be the last to be interrupted. When a live conductor comes into contact with the enclosure connected to the protective conductor, it will normally cause a "short circuit to frame" that will trip the fuse, a circuit breaker or a residual-current-operated circuit breaker and so disconnect the circuit.

Grounding without a special grounding conductor is sometimes a feature of older installations, i.e. the N and PE conductors are connected in the socket. This is now prohibited for new installations with conductors smaller than 10 mm² copper/16 mm² aluminum. In such cases, the N and PE conductors shall be routed separately.