Control engineering - definition of terms and fundamental principles 5.17 Classes Further methods of protecting against direct contact Another method of protecting humans and livestock against direct contact or indirect contact with live parts is to use suitable voltage sources: SELV PELV FELV Note SELV, PELV and FELV are described in detail in IEC 60364-4-41. IEC 60204-1 only refers to PELV. That means that PELV in the machine shall be set up according to the rules of IEC 60204-1. If SELV or FELV is to be implemented in the machine, this shall be done according to the rules of IEC 60364-4-41.

Control Panels compliant with IEC Standards and European Directives 72 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 Class Meaning II Protective insulation Equipment in class II has reinforced or double insulation between the mains circuit and the output voltage or metal enclosure; it is not connected to the protective conductor. This measure is also known as "protective insulation". Even if the equipment has electrically conductive surfaces, it is protected against contact with live parts by two layers of insulating material. Mobile devices in class II do not have a plug with protective contact. Plugs without a protective contact are used to connect the equipment to the mains.

Contoured plugs that look similar to shock-proof plugs are used in Germany for high currents. "Euro" plugs are used for low currents (up to 2 A). A "double square" symbol on an electrical device / enclosure indicates that it has protective insulation. III Class III equipment operates on safety extra-low voltage (SELV). In line-fed operation, it also requires reinforced or double insulation between the mains circuit and the output voltage.