Control engineering - definition of terms and fundamental principles 5.17 Classes SELV (Safety Extra Low Voltage) IEC 60364-4-41 describes SELV as safety extra-low voltage lower than 50 V (alternating voltage) or 120 V (direct voltage) generated by a safety transformer as defined by EN 61558-2-6. This also applies to power supply units with integral safety transformer. Safety transformers are designed such that the HV and LV sides are electrically isolated from one another, i.e. so that parasitic voltages cannot be transferred between them. The following current sources are also suitable if it has been ensured that the control circuit is safely isolated from the power circuit:
An electrochemical current source (e.g. a battery) or another current source that is safely isolated from circuits with higher voltage (e.g. a generator driven by an internal combustion engine). Certain electronic devices constructed according to relevant standards and with which the voltage does not rise above the permitted values even as a result of the occurrence of a fault. Mobile low-voltage current sources (e.g. safety isolating transformers or motor generators) shall have double or reinforced insulation as defined by IEC 60364-4-41. The low-voltage side is not grounded with SELV.
Safety transformer or equivalent power source No connection to ground Figure 5-12 SELV According to IEC 60364-4-41, SELV can be regarded as effective protection against direct contact in dry environments provided that the voltage does not exceed 25 V AC or 60 V DC. Note Safety extra-low voltages drawn from batteries or accumulators comply with the requirements of class III without any additional measures. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 73