Control engineering - definition of terms and fundamental principles 5.17 Classes PELV (Protective Extra Low Voltage) Protective extra-low voltage with protective separation. Similar concept to SELV, but the equipment is grounded on the secondary side. Figure 5-13 PELV IEC 60204-1 describes PELV as protection against electric shock as follows: Rated voltage ≤ 25 V AC or 60 V DC in dry locations and when large area contact of live parts with the human body is not expected. ≤ 6 V AC or 15 V DC in all other cases. The PELV circuit shall be grounded. The PELV circuit shall be electrically separated from other live circuits.

As a minimum, as with a safety isolating transformer (see IEC 61558-1 and IEC 61558-2-6) Physical separation of the conductors. Where this requirement is impracticable, suitable barriers shall be used for separating the conductors where there are circuits of varying voltage or all cables in the cable duct are approved for the highest occurring voltage. Plugs and socket-outlets shall not be capable of combination with other circuits. Power sources as with SELV FELV (Functional Extra Low Voltage) Functional extra-low voltage without protective separation. Same voltage limits as for SELV, but no special requirements of the transformer or the power supply unit.

Used mostly for general control systems. Not a safety power source. Ground connection permitted. Figure 5-14 FELV Control Panels compliant with IEC Standards and European Directives 74 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002