Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device 6.2 Incoming supply conductor termination and supply disconnecting device 6.2.1 Incoming supply conductor termination Areas of responsibility The incoming supply conductor termination represents the power supply, i.e. the supply of electrical power, for the machine. Unless otherwise agreed between the user and the machine supplier, the area of responsibility of the machine supplier begins at the point at which the machine is connected to the incoming supply, In other words, at the infeed terminal of the supply disconnecting device or, if provided, at upstream connecting terminals.
If a switch disconnector without fuses is used as a supply disconnecting device, the outgoing cables at the supply disconnecting device will not have any protection. In this case, the supplier shall specify that the operator uses suitable fuses upstream of the control panel. Figure 6-1 Defining boundaries between areas of responsibility of user and supplier In order to reduce the risks associated with electrical installations, Chapter 5.1 of IEC 60204-1 recommends the use of only one incoming supply conductor wherever this is practicable. Control Panels compliant with IEC Standards and European Directives 82 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002