HiPhi — 6.2.1 Incoming supply conductor termination

Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Electrical equipment of a machine Where another supply is necessary, e.g. for circuits that operate at a different voltage (control circuits, etc.), that supply should be derived, as far as is practicable, from devices that form part of the electrical equipment of the machine. Depending on the complexity of the machinery, there may also be a need for more than one incoming supply conductor, for example, for large, complex machinery (e.g. optional generator operation, UPS systems). As a general rule, however, the number of supply conductors should be kept to the absolute necessary minimum.

If a neutral conductor is used, a separate insulated terminal labeled "N" shall be provided. Such a terminal can also be part of the supply disconnecting device. In this case, there shall be no connection between the neutral conductor and the protective bonding circuit inside the electrical equipment. Note Exception for TN-C and TN-C-S systems A connection may be made between the neutral terminal and the PE terminal at the point of the connection of the electrical equipment to a TN-C or TN-C-S supply system. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 83