HiPhi — 6.2.1 Incoming supply conductor termination

Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device For types of grounding system (Page 47) in which an external protective conductor is routed to the machine, the protective conductor shall be connected to a terminal that is in the same terminal compartment as the associated line conductor terminals. The terminal for the external protective conductor shall be marked with "PE". Figure 6-2 Separate terminals for neutral conductor and protective conductor Control Panels compliant with IEC Standards and European Directives 84 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002