Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Protective conductor Protective conductors made of copper require terminals dimensioned for a cross-sectional area specified in the table below. Table 6- 1 Minimum cross-sectional area of copper protective conductors Source: IEC 60204-1, Table 1: Minimum cross-sectional area of copper protective conductors External protective conductors of a material other than copper may be used if they have a cross-sectional area of at least 16 mmІ.
Where a protective conductor of a material other than copper is used, the terminal size shall be selected to suit the cross-sectional area of the conductor and shall be suitable for the conductor material selected. You can find information about dimensioning aluminum protective conductors in the Chapter Protective bonding (Page 158). The terminal for the external protective grounding system or the external protective conductor shall be labeled with the letters PE. Figure 6-3 Example:
Labeling of terminal for the external protective conductor Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 85 Cross-sectional area of the conductor S (mm2) Minimum cross-sectional area of the corresponding copper protective conductor Sp (mm2) S ≤ 16 S 16 16 S > 35 S /2