Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Supply disconnecting devices supplied by Siemens Siemens offers a large portfolio of suitable supply disconnecting devices (Page 234). Switch disconnectors compliant with IEC 60947-3 Figure 6-4 Selection of Siemens switch disconnectors compliant with IEC 60947-3 Circuit breakers compliant with IEC 60947-2: Figure 6-5 Selection of Siemens circuit breakers compliant with IEC 60947-2 Rule It shall have a visible position indicator that clearly shows whether the supply disconnecting device is ON or OFF. The following conditions shall be fulfilled for this purpose:
There shall only be one OFF position and one ON position. The OFF position is marked with "O" and the ON position with "I", or there shall be a visible contact gap. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 87