Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device 6.2.4 Devices for removal of power for prevention of unexpected start-up Machines or parts of machines may often need to be serviced at regular intervals. To ensure that maintenance engineers can work in safety, it may be necessary to shut down the machine or parts of the machine. In Chapters 5.4 and 5.5 of IEC 60204-1, a distinction is made between "Devices for removal of power for prevention of unexpected start-up" and "Devices for isolating electrical equipment (Page 98)".
Whenever a potentially hazardous situation as a result of unexpected movement of a machine or part of a machine can develop, suitable "Devices for removal of power for prevention of unexpected start-up" shall be provided. This can be achieved by several methods, including by the supply disconnecting device itself. If only part of the machine needs to undergo maintenance while the rest remains in operation, it may be necessary to provide additional devices. Devices of this kind shall be placed in appropriate locations and be readily identifiable as to their purpose and function. Figure 6-11 Example:
Device for removal of power for prevention of unexpected start-up Note A permanent marking/label as to their purpose and function can also be affixed. If a device for removal of power with isolation function is required, devices also approved as Supply disconnecting (isolating) device (Page 86) may be used. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 95