Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Equipment with fuse links Note Disconnectors, plug-in fuses and isolating links may only be used in enclosed electrical operating areas to which only skilled persons have access. Figure 6-12 Example: Device with plug-in fuses If access is prohibited to all except skilled persons by the fact that the devices are installed in enclosed operating areas, then the devices in question can also be deployed as "devices for removal of power for prevention of unexpected start-up".
Background An unqualified person cannot always tell which switch belongs to which piece of equipment, or may not be able to correctly interpret the relevant circuit diagram. Furthermore, the enclosed operating area will prevent unauthorized closure of disconnectors. Devices without isolation function Devices without isolation function may also be used. However, such devices may only be used for removal of power prior to inspections and adjustment work on non-electrical equipment, or for work on electrical equipment under the following conditions: There is no risk of electric shock or burns. The device for removal of power remains effective throughout the work.
The work is of a minor nature which does not involve disturbing existing wiring of components. Note Devices without isolation function are, for example, a contactor de-energized by a control circuit or a power drive system (PDS, Power Drive System) with the function "Safe Torque Off" (STO, Safe Torque Off) in accordance with IEC 61800-5-2. Control Panels compliant with IEC Standards and European Directives 96 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002