Deploying as a Web Application 2. Be sure the project tags are properly set to either Server or Local. If the tags are to be exposed to the Web Client, then set them to Server , otherwise set to Local . Step 3: Develop your Screens and create HTML screens 1. Develop your project screen. Depending on your Thin Client screen size, you may want to develop a separate set of screens with a different resolution. Auto Screen scaling is supported (enabled in a prior step), but auto screen scaling naturally has limitations. 2. Save and close all project screens. 3. Be sure you have defined a Startup Screen ( Viewer on the Project tab of the ribbon). 4.
You can save individual screens as HTML by selecting the Save as HTML or Save Screen Group as HTML options in the Application menu, or save all Screens and Screen Groups as HTML by selecting the Save All as HTML option. 5. If you are just updating a Screen, and especially when you make any configuration changes to the Web settings, you should run the Verify Project tool (i.e., on the Home tab of the ribbon, in the Tools group, click Verify ). 6. The HTML (web) pages will be stored in the Web sub-folder of your project folder. Step 4: Install NTWebServer 1. NTWebServer is InduSoft's lightweight Web Server for Windows NT/XP/2000/Server 2003/Vista environments.
NTWebServer.exe is found in […]\InduSoft Web Studio v7.0\Bin 2. Copy NTWebServer.exe from the \Bin folder and paste it into the Web sub-folder of your project folder. 3. From the Web sub-folder, double click on NTWebServer to start it. 4. A new window should pop-up. At the bottom, there should be a message indicating that NTWebServer is listening. If a message appears that NTWebServer failed to open a socket, it is most likely caused by Microsoft IIS (Web Server) running in a background mode. If this is the case, you will need to stop IIS, and then restart NTWebServer Tip: A Web server typically operates on, or "listens to," a computer's TCP/IP port 80.
Only one running process can listen to a given port, so if another process on your computer — for example, some third-party SCADA software — is already listening to port 80, then it and the Web server process may conflict with each other. You must either configure one of the processes to listen to a different port or use Task Manager to end the conflicting process. If you cannot identify the conflicting process, then in Windows, open Command Prompt and enter the following command to get a list of all networking processes: netstat -a -o Step 5: Start the runtime project 1. On the Home tab of the ribbon, click Run . Step 6: Launch Microsoft Internet Explorer and connect to the Web Server 1.
Click on the Start button (or Alt Tab) to access the Microsoft Internet Explorer program. 2. Start Internet Explorer, and type the address of the starting (home webpage). E.g. http://127.0.0.1/ startup.html 3. Note that the startup.sg (or whatever your startup display or screen group name is) will have a HTML file extension on it when accessed from Internet Explorer. 4. Sign on as Guest with no password, assuming no security has been enabled. Procedure B: Thin Client using NTWebServer, Network IP Once Procedure A has been completed, the next step is to enable network connected Thin Clients, instead of using the local loopback.
You need to know the IP address of your PC, as seen from the network. You can get this information from the Network Settings in the Control Panel, or putting the function GetComputerIP() in a Rectangle Object on a screen and running the project. Step 1: Configure IWS Settings 1. Stop any active runtime project. 2. On the Project tab of the ribbon, in the Web group, click Thin Client . In the Data Server IP Address field, enter the IP address of your PC (as viewed from the network). E.g. 192.168.1.100 InduSoft Web Studio Page 363