The device is equipped with a reset push button, three LEDs and terminal blocks for the AC, KNX bus line and ancillary output.
KNX-20E-640 Installation Manual Introduction The KNX Power Supply KNX-20E-640 is a 640mA power supply with high efficiency and a small footprint of only 3SU (52.5mm). The device has a KNX bus choke output and an additional output for ancillary power. The -5 ~ +50 wide temperature operating range can meet all kinds of applications. LED indicators are used in case of normal operation, overload conditions and RESET operation. It is perfectly suitable to power up any products labeled with the KNX trademark.
Features EIB/ KNX power supply with integrated choke Cooling by free air convection Compact size with 3US (52.5mm) width Safety extra low voltage (SELV) LED indicator for normal operation, bus reset and bus overload Isolation class Ⅰ 180 ~ 264Vac input Installed on DIN TS-35/7.5 or 15 No load power consumption 200ms mains failure back-up time 3 years warranty Protections: Short circuit/ Overload (short-circuit-proof)/ Over voltage Display The device is equipped with a reset push button, three LEDs and terminal blocks for the AC, KNX bus line and ancillary output. 1 KNX bus terminal (Red : BUS +V, Black :
BUS -V) 2 Ancillary power terminal 3 RESET button 4 Power ON (Green) 5 Reset (Red) 6 Ⅰ > Ⅰ max (Red) 7 AC terminal (L,N, ) http://www.meanwell.com
Installation
Installation 1. Wiring Use wires with an adequate cross-section Use suitable mounting tools to do the wiring and mounting The maximum number of bus devices connected is 64 The maximum length of a line segment is 350 m, measured along the line between the power supply and the furthest bus device The maximum distance between two bus devices cannot exceed 700 m The maximum length of a bus line is 1000 m, keeping into account all segments 2. Mounting and Connection a. Insert the power supply onto the DIN rail (TS35/7.5 or TS35/15). Click b. Connect the KNX, the connection to the KNX bus line is made with the terminal block (red: BUS +V/ black:
BUS -V ) located on the left upper part of the front. c. Connect the mains voltage, the connection to the AC is made with the terminal (L, N, ) located on the bottom. http://www.meanwell.com AC Type (L, and ancillary power terminals N, , +V, -V) KNX bus terminal (BUS +V, BUS -V) Solid wire 0.5 ~ 4.0mm 0.6 ~ 0.8Φ Stranded wire 0.5 ~ 2.5mm2 ------ American wire gauge 12 ~ 26AWG 20 ~ 22AWG Wire stripping length 6.5 mm (0.255") 5mm (0.196”) Screwdriver 3m m Slotted ----- Recommended tightening torque 8 k gf-cm (7 lb-in) -----
Cautions
3. MCB Use a MCB (miniature circuit breaker) with an adequate current rating to protect the KNK device. Function and Operation Note: These calculated values are based on MCB S201 series manufactured by ABB. The device does not require any configuration with ETS® (Engineering Tool Software) tool. Once the wiring is proper done, the “Power on” LED will light up and the rest of the LEDs remain off to indicate that the unit is in operation condition. Reset: To carry out a reset, press the RESET button for at least 20 seconds to reset the KNX power supply. Fault: If the red LED ( I > I max ) lights up with applied mains voltage, a fault is present.
This means that the KNX output is overloaded or connected to the line. Once the fault has been rectified, carry out a reset by pressing the RESET button for approx. 20 seconds. shot-circuited. The problem can be solved by removing the cause of the short circuit or by reducing the number of KNX devices Meaning of the LEDs Environmental Limitations Always allow adequate ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit in use to prevent it Maximum ambient temperature must not exceed 50℃ from overheating Only install the unit in indoor environments Cautions It should be ensured that the supply can be isolated when connecting the unit.
This unit must be installed by a qualified electrician Environmental declaration information https://www.meanwell.com//Upload/PDF/RoHS_PFOS.pdf https://www.meanwell.com//Upload/PDF/Declaration_RoHS-E.pdf https://www.meanwell.com//Upload/PDF/REACH_SVHC.pdf http://www.meanwell.com Model B10 B16 C10 C16 KNX-20E-640 1 2 2 4 Power ON (GREEN) Reset (RED) I > Imax (RED) Status ON OFF OFF Ready for operation or working normally OFF ON OFF Resetting ON OFF ON Output current too high OFF OFF ON Short-circuit or bus reverse polarity OFF OFF OFF No mains voltage