Victron Energy Lithium NG 12,8V — 3.3.3. The VE.Bus BMS NG

Lithium NG 12,8V battery manual 3.3.3. The VE.Bus BMS NG The VE.Bus BMS NG is a Battery Management System (BMS) designed specifically for Victron Energy Lithium NG batteries (not to be confused with Lithium Smart batteries without NG designation). These are LiFePO ₄ batteries available in 12,8 V, 25,6 V, and 51,2 V, and in various capacities. The VE.Bus BMS NG is intended to interface with and protect Victron Lithium NG batteries in systems that include a Victron VE.Bus inverter/charger or VE.Bus inverter. It relies on this connection to perform key functions such as enabling/disabling charge and discharge based on battery conditions.

Just like the smallBMS NG, it also features a “load disconnect”, a “charge disconnect” and a "pre-alarm" contact. In the event of low cell voltage, the VE.Bus BMS NG will send a “load disconnect” signal to turn off the load(s) and will also disable inverting of the inverter/charger via VE.Bus communication. Prior to turning loads off, it will send a pre-alarm signal warning of imminent low cell voltage. In the event of a high cell voltage or high/low battery temperature, the VE.Bus BMS NG will send a “charge disconnect” signal to turn the charger(s) off and it will also disable the charger of the inverter/charger.

A mains detector and a short RJ45 UTP cable ship together with the VE.Bus BMS NG. These are needed for mains detection once the inverter/charger has been turned off by the BMS. The mains detector is not needed for the MultiPlus-II or Quattro-II series of inverter/chargers. For more information see the VE.Bus BMS NG manual which can be found on the VE.Bus BMS NG product page . The VE.Bus BMS NG will turn loads and chargers off via “load disconnect”, and “charge disconnect” and controls the inverter/charger VE.Bus BMS NG, VE.Bus BMS Mains detector and RJ45 UTP cable System design and BMS selection guide Page 8