© Siemens AG 2010 Solid-State Switching Devices for Resistive Loads 3RF29 Function Modules SIRIUS power controllers for 3RF Overview Application Power controllers for 3RF2 single-phase solid-state switch- ing devices The power controller can be used for: • Complex heating systems • Inductive loads • Loads with temperature-dependent resistor • Loads with ageing after long-time service • Simple indirect control of temperature The power controller is a function module for the autonomous power control of complex heating systems and inductive loads. The following functions have been integrated: • Power controller for adjusting the power of the connected load.
Here, the setpoint value is set with a rotary knob on the module as a percentage with reference to the 100 % power stored as a setpoint value. • Inrush current limitation: With the aid of an adjustable voltage ramp, the inrush current is limited by means of phase control. This is useful above all with loads such as lamps or infrared lamps which have an inrush transient current. • Load circuit monitoring for detecting load failure, partial load faults, alloyed power semiconductors, lack of voltage or a break in the load circuit. The power controller can be used on the instantaneously switch- ing 3RF21 and 3RF23 solid-state switching devices (single- phase).
If only the full-wave operating mode is used, the power controller can also be used on the "zero-point switching" solid- state relays and contactors. Power control The power controller adjusts the power in the connected load by means of a solid-state switching device depending on the set- point selection. It does not compensate for changes in the mains voltage or load resistance. The setpoint value can be predefined externally as a 0 to 10 V signal or internally by means of a poten- tiometer. Depending on the setting of the potentiometer ( t R ), the control is carried out according to the principle of full-wave con- trol or generalized phase control. Note:
With the phase control operating mode, a partial load fault is de- tected by cyclic "scanning" of the load; the exact mode of oper- ation is described in the data sheets! 4 Special versions: deviations from the standard version Full-wave control In this operating mode the output is adjusted to the required set- point value changing the on-to-off period. The period duration is predefined at one second. 3RF29 04-0KA13-0KC0 During the teaching process the connected solid-state relay or contactor is not activated; i. e. no current flow takes place. No current reference value is stored. No part-load monitoring!
Generalized phase control 3RF29 ..-0KA1.-0KT0 In this operating mode the output is adjusted to the required set- point value by changing the current flow angle. In order to ob- serve the limit values of the conducted interference voltage for industrial networks, the load circuit must include a reactor with a rating of at least 200 μH. No part-load monitoring! Selection and ordering data Rated control supply voltage 24 V AC/DC 4 110 … 230 A 1 1 unit 101 0.175 4 A 1 1 unit 101 0.175 20 A 1 1 unit 101 0.175 50 A 1 1 unit 101 0.175 90 A 1 1 unit 101 0.175 20 400 …
600 A 1 1 unit 101 0.175 50 A 1 1 unit 101 0.175 50 A 1 1 unit 101 0.175 90 A 1 1 unit 101 0.175 4/71 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Rated operational Rated operational DT current Ie voltage Ue A V Order No. Price per PU PU PS* PG Weight (UNIT, per PU SET, M) approx. kg Weight per PU approx. Power controllers Rated operational current Ie Rated operational voltage Ue 3RF29 04-0KA13-0KC0 3RF29 04-0KA13-0KT0 3RF29 20-0KA13 3RF29 50-0KA13 3RF29 90-0KA13 3RF29 20-0KA16 3RF29 50-0KA16 3RF29 50-0KA16-0KT0 3RF29 90-0KA16 Version DT Order No. Price per PU PU PS* PG Weight (UNIT, per PU SET, M) approx. kg Weight per PU approx.
Optional accessories 3RF29 00-0RA88 1 10 units 101 0.001 Sealable covers B for function modules (not for converters) 3RF29 00-0RA88 3RF29 00-0RA88