© Siemens AG 2010 BETA Measuring Three-Phase Measuring Devices 7KT1 39 LAN couplers Overview Benefits A LAN coupler supports the worldwide data recall of up to 10 multicounters and E-counters over a LAN link to the Internet.

Integration of measuring devices in industrial or office commu- nication Display of measured data using the standard software MS Ex- cel Use of existing local networks (LAN) for transmitting the mea- sured data TCP/IP data protocol enables a wide range of applications Limit value signals with time information for all measured val- ues increases your plant's safety Open software structure enables the implementation of cus- tomized solutions for measured data indication and analysis Worldwide communication of the measured values via LAN One LAN coupler for 10 devices The LAN coupler is used in conjunction with multicounters and E-counters. Up to 10 devices can be linked with a LAN coupler.

In turn, the LAN coupler is connected to a LAN. Data communication between the LAN coupler and the PC takes place using the TCP/IP protocol. The supplied software can be used to call up the measured data over LAN coupler and transfer it to a PC. The measured data are continuously stored as a text file with time and date stamp. This gives users great flexibility in designing their own solutions (e. g. the data can be prepared using MS Excel). Selection and ordering data More information Connection of the LAN coupler to a LAN Connection of measuring devices to the LAN coupler Each station in a LAN must be assigned its own IP address.

On delivery, or after a reset, the LAN coupler has a standard IP ad- dress. The new IP address must be set in the LAN coupler dur- ing start-up. To do this, the LAN coupler must be directly con- nected to a PC using a so-called "cross-over" cable. This is a network cable in which the transmit and receive wires are cross- connected. This creates a small LAN with 2 stations, PC and LAN coupler can communicate with each other directly. The supplied LAN coupler configuration tool must be installed on the PC. This direct connection can then be used to set a new IP ad- dress in the LAN coupler, as well as other network parameters, such as subnet mask and default gateway.

The LAN coupler must then be connected to the target system as communication is subsequently only possible with the new settings. E-counters and multicounters are connected to the LAN couplers over their communication interface. The network is an RS 485 network in which devices are connected over a shielded 2-wire cable. When using Modbus, the device address and transmission rate must be set in the multicounters. This is not necessary if using the multicounters and E-counters over the LAN coupler, as the LAN coupler automatically detects and identifies any connected E-counters and multicounters.

You can now use the LAN coupler configuration tool (over the LAN net- work) to tell the LAN coupler from which device you want to re- trieve the measured data. The LAN coupler carries out a so-called "polling" during runtime. This cyclically retrieves the most recently gathered measured data from the measuring devices and buffers them in the LAN coupler. This can then be called up at any time over the LAN. 19 19/137 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Uc V AC MW Order No. Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg Weight per PU approx. V AC LAN couplers For connection of up to 10 devices over RS485 Software tools included for:

• Installation and commissioning • Data transmission and storage • MS Excel macro for visualization of measured data 230 4 B 1 1 027 0.232 7KT1 390