Manual - BMV-712 Smart 7.3. Relay settings The battery monitor is equipped with a programmable relay. These settings are used to program the function of the relay. The relay settings are disabled by default (except the State of Charge (SoC) relay setting). To enable, a relay setting do the following: In the VictronConnect app, enable the relay setting by sliding the slider button to the right. Via the head unit, enable the relay setting by changing the set and clear value to any value above zero. 7.3.1. Relay mode This setting has the following relay modes, namely: 7.3.2.
Invert relay This function enables selection between a normally de-energised (contact open) or a normally energised (contact closed) relay. When inverted, the open and closed conditions as described in all the relay settings are inverted (with the exception of the Relay state [32] ). Note that the "normally energised" setting will slightly increase the power consumption of the battery monitor. 7.3.3. Relay state This is a read-only parameter and it displays whether the relay is open or closed (de-energised or energised). 7.3.4. Relay minimum closed time Sets the minimum time the "closed" condition will remain present after the relay has been energised.
Note that this changes to "open" and de-energised if the relay function has been inverted ( Invert relay [32] setting). An application example is to set a minimum generator run time when the relay is set to "charger" mode ( Relay mode [32] setting). Page 32 All features and settings Setting Default mode Modes Description DFLT Default mode. The relay settings 16 up to 31 can be used to control the relay. Relay mode (setting 11) DFLT CHRG Charger mode. The relay will close when the state of charge falls below setting 16 (discharge floor) or when the battery voltage falls below setting 18 (low voltage relay).
The relay will be open when the state of charge is higher than setting 17 (clear state of charge relay) and the battery voltage is higher than setting 19 (clear low voltage relay). An application example is to start and stop control of a generator, together with settings 14 and 15. REM Remote mode. The relay can be controlled via the VE.Direct interface. Relay settings 12 and 14 up to 31 are ignored as the relay is under the full control of the device connected via the VE.Direct interface.
Setting Default mode Modes Range Invert relay (setting 12) OFF OFF Normally de-energised ON Normally energised Setting Value Description Relay state (setting 13) OPEN The relay is open (de-energised) CLSD The relay is closed (energised) Setting Default Range Step size Relay minimum closed time (setting 14) 0 minutes 0 - 8 hours 1 minute