Manual - BMV-712 Smart 7.3.5. Relay off delay Sets the amount of time the "de-energise relay" condition must be present before the relay opens. An application example is to keep a generator running for a while to charge the battery better when the relay is set to "charger" mode ( Relay mode [32] setting). 7.3.6. Low State of Charge (SoC) relay When the state of charge percentage has fallen below the "set relay" value, the relay will close. When the state of charge percentage has risen above the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings).
The "clear relay" value needs to be greater than the "set relay" value. When the "set relay" and "clear relay" values are equal, the state of charge condition will be unable to drive the relay. Note that this setting is also known as the discharge floor. The time-to-go reading displayed by the battery monitor relates to this setting. The time to go is the time left until this setting (the discharge floor) has been reached. 7.3.7. Low voltage relay When the battery voltage falls below the "set relay" value for more than 10 seconds the relay will close.
When the battery voltage rises above the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). The "clear relay" value needs to be greater than the "set relay" value. 7.3.8. High voltage relay When the battery voltage rises above the "set relay" value for more than 10 seconds the relay will close. When the battery voltage falls below the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). The "clear relay" value needs to be greater than the "set relay" value. 7.3.9.
Low starter voltage relay This setting is available if the aux input has been set to "Starter battery", see the Aux input [40] setting. When the auxiliary (e.g. starter battery) voltage falls below "set relay" value for more than 10 seconds, the relay will be closed. When the auxiliary voltage rises above the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). The "clear relay" value needs to be greater than the "set relay" value.
Page 33 All features and settings Setting Default Range Step size Relay off delay (setting 15) 0 minutes 0 - 500 minutes 1 minute Setting Default Range Step size Set relay value (setting 16) 50% 0 - 99% 1% Clear relay value (setting 17) 90% 0 - 99% 1% Setting Default Range Step size Set relay value (setting 18) 0V 0 - 95V 0.1V Clear relay value (setting 19) 0V 0 - 95V 0.1V Setting Default Range Step size Set relay value (setting 20) 0V 0 - 95V 0.1V Clear relay value (setting 21) 0V 0 - 95V 0.1V