Manual - BMV-712 Smart 7.3.10. High starter voltage relay This setting is available if the aux input has been set to "Starter battery", see the Aux input [40] setting. When the auxiliary (e.g. starter battery) voltage rises above the "set relay" value for more than 10 seconds, the relay will be closed. When the auxiliary voltage falls below the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). The "clear relay" value needs to be greater than the "set relay" value. 7.3.11.
Low temperature relay This setting is available if the aux input has been set to "Temperature", see the Aux input [40] setting. Use the Temperature unit setting [42] to choose between °C or °F temperature units. When the battery temperature drops below the "set relay" value for more than 10 seconds the relay will close. When the battery temperature rises above the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). This setting is available if the aux input has been set to "Mid point", see the Aux input [40] setting. 7.3.12.
Mid voltage relay See the chapter Midpoint voltage monitoring [46] for more information about the midpoint voltage. When the midpoint voltage deviation rises above the "set relay" value, the relay will close. When the midpoint voltage deviation falls below the "clear relay" value, the relay will open (after a delay, depending on the Relay minimum closed time [32] and/or the Relay off delay [33] settings). 7.4. Alarm settings The BMV battery monitor is equipped with an alarm relay and a buzzer. Alarms are also visible on the VictronConnect app while connected to the battery monitor or are used to send an alarm signal to a GX device. Alarms are disabled by default. To enable do the following:
In the VictronConnect app, enable the alarm by sliding the slider button to the right. Via the head unit, enable the alarm by changing the "set" and "clear" value in the alarm settings to any value above zero. When enabled (set to ON), the buzzer will sound an alarm as soon as an alarm condition occurs. After a button is pressed, the buzzer will stop sounding. 7.4.1.
Alarm buzzer Page 34 All features and settings Setting Default Range Step size Set relay value (setting 20) 0V 0 - 95V 0.1V Clear relay value (setting 21) 0V 0 - 95V 0.1V Setting Default Range Step size Set relay value (setting 24) 0V 0 - 95V 0.1V Clear relay value (setting 25) 0V 0 - 95V 0.1V Setting Default Range Step size Set relay value (setting 28) 0°C 0°F -40 - +99°C -40 - +210°F 1°C 1°F Clear relay value (setting 29) 0°C 0°F -40 - +99°C -40 - +210°F 1°C 1°F Setting Default Range Step size Set relay value (setting 30) 0% 0 - 99% 1% Clear relay value (setting 31) 0% 0 - 99% 1%