omron — 2-4-3 Settings for each Unit

2 Installing the NB Unit and Connecting Peripheral Devices 2-4 Serial Communication Connection 2-4-3 Settings for each Unit When connecting with the serial communication ports, the settings for each Unit are as follows: CP1L-L14/L20/M30/M40/M60 models CP1H-X40/XA40/Y20 models CP1E-N14/N20 models CP1E-N30/N40/N60/NA20 models CP1L-EL20/EM30/EM40 models CP2E-N14/N20 models CP2E-N30/N40/N60 models CP2E-S30/S40/S60 models CP2E-E14/E20 models CP2E-E30/E40/E60 models  PLC System Settings Area 2-4-3 Settings for each Unit Write settings directly into the [PLC System Settings Area] with a peripheral tool (CX-Programmer, etc.) based on the model and port of the host. *1 The channel No.

of CP1L/H is PLC Setup area. *2 The communication speed should be set to the same value as that of the NB Unit. *3 The NB cannot be connected to the CP2E series Built-in RS-485 Port (2-wire).  Settings for the front-side DIP Switches Set the front-side DIP switches so as to validate the settings for [PLC System Settings Area]. Set the SW4 to OFF when serial port 1 is used, set SW5 to OFF when serial port 2 is used. As the CP1L-L has only one serial port, it has no DIP switch SW5. NB-series Programmable Terminals Setup Manual(V107) 2-13 When connecting to CP-Series CPU Units 2 Host model and Port No. Channel No.

(*1) Write Value Setting CP1L-M30/M40/M60, serial port 1 CP1H-X40/XA40/Y20, serial port 1 CP1L-EM30/EM40, serial port 1 144 8000 Use Host Link 145 0000~000A(*2) Communication speed 147 0000~001F Unit number CP1L-L14/L20, serial port 1 CP1L-M30/M40/M60, serial port 2 CP1H-X40/XA40/Y20, serial port 2 CP1L-EL20, serial port 1 CP1L-EM30/EM40, serial port 2 160 8000 Use Host Link 161 0000~000A(*2) Communication speed 163 0000~001F Unit number Host model and Port No. Channel No.

Write Value Setting CP1E-N14/N20, serial port 1 CP1E-N30/N40/N60/NA20, serial port 1 CP2E-S30/S40/S60, Built-in RS-232C Port CP2E-E14/E20, Built-in RS-232C Port CP2E-E30/E40/E60, Built-in RS-232C Port CP2E-N14/N20, serial port 1 CP2E-N30/N40/N60, serial port 1 A617.15~12 0 Use Host Link A617.11~08 0, 3~A(*2) Communication speed A617.07~00 00 7 data bits, 2 stop bits, Even CP1E-N30/N40/N60/NA20, serial port 2 CP2E-N30/N40/N60, serial port 2 (*3) A618.15~12 0 Use Host Link A618.11~08 0, 3~A(*2) Communication speed A618.07~00 00 7 data bits, 2 stop bits, Even ON 1 2 3 4 5 6 ON 1 CP1L-M 2 CP1H CP1L-L 3 4