omron — 2-4-3 Settings for each Unit

2 Installing the NB Unit and Connecting Peripheral Devices C200HX/HG/HE(-Z), CPM1  , CPM2  , CQM1H type CPU Units  Connection Methods The connection methods for the CPU Units of different PLC models.  PLC System Settings Area Write settings directly into the [PLC System Settings Area] (Data memory) with a peripheral tool (CX- Programmer, etc.) based on the model and port of the host. For RS-232C *1 The RS-232C port of the Communication Board. *2 The RS-232C port of the Serial Communication Board. *3  is the set value of the communication speed. Set the communication speed to the same value as that of the NB Unit. *4 Standard settings of the Communication conditions are as follows:

Start bit: 1 bit, Data bit: 7 bit, Stop bit: 2 bit, parity check: even 2-14 NB-series Programmable Terminals Setup Manual(V107) When connecting to C-Series CPU Units PLC Models RS-232C connection RS-422A connection C200HX/HG/HE(-Z) • Connect to the RS-232C port built in the CPU Unit • Connect to the RS-232C port (Ports A, B) of the serial communication board • Connect to the RS-422A port (port A) of the serial communication board CPM1A • Connect to the peripheral port with a dedicated RS-232C adaptor (CPM1-CIF01). • Connect to the peripheral port with a dedicated RS-422A adaptor (CPM1-CIF11 type).

CPM2A • Connect to the RS-232C port built in the CPU Unit • Connect to the peripheral port with a dedicated RS-232C adaptor (CPM1-CIF01). • Connect to the peripheral port with a dedicated RS-422A adaptor (CPM1-CIF11 type). CPM2C • Connect to the RS-232C port built in the CPU Unit or the peripheral port with a dedicated conversion cable (CPM2C-CN111 type, CS1W- CN118 type and CS1W-CN114 type) (CPM2C- CN111 type is a cable that divides the Unit port into the RS-232C port built in the CPU Unit and the peripheral port.

When connecting to the peripheral port, a RS-232C adaptor (CPM1- CIF01 type) is also needed to be connected.) • Connect to the peripheral port with a dedicated conversion cable (CPM2C-CN111 type or CS1W- CN114 type) and a RS-422A adaptor (CPM1-CIF11 type) (CPM2C-CN111 type is a cable that divides the Unit port into the RS-232C port built in the CPU Unit and the peripheral port). CQM1H • Connect to the RS-232C port built in the CPU Unit • Connect to the peripheral port with a conversion cable (CS1W-CN118 type) Connect to the RS-232C port (Port 1) of the serial communication board • Connect to the RS-422A port (Port 2) of the serial communication board Host Model Channel No.

Write Value Setting The RS-232C port built in C200HX/HG/HE(-Z), CPM2A, CPM2C, CQM1H DM6645 0001 Use Host Link DM6646 03(*3) Communication conditions are standard settings. (*4) DM6648 0000 Unit No. 00 CPM1A DM6650 0001 Use Host Link DM6651 03(*3) Communication conditions are standard settings. (*4) DM6653 0000 Unit No. 00 Port A of C200HX/HG/HE(-Z) (*1) Port 1 of CQM1H (*2) DM6555 0001 Use Host Link DM6556 03(*3) Communication conditions are standard settings. (*4) DM6558 0000 Unit No. 00 Port B of C200HX/HG/HE(-Z) (*1) DM6550 0001 Use Host Link DM6551 03(*3) Communication conditions are standard settings. (*4) DM6553 0000 Unit No. 00