2 Installing the NB Unit and Connecting Peripheral Devices For RS-422A 2-4 Serial Communication Connection *1 The RS-422A port of the Communication Board *2 The RS-422A port of the Serial Communication Board *3 is the set value of the communication speed. Set the communication speed to the same value as that of the NB Unit. *4 Standard settings of the Communication conditions are as follows: Start bit: 1 bit, Data bit: 7 bit, Stop bit: 2 bit, parity check: even For operations on [PLC System Settings Area], refer to the manual of the PLC employed.
2-4-3 Settings for each Unit Additional Information When the NB Unit communicates with the C-Series via Host Link while the PLC is in the Run mode, the mode will be automatically switched to the Monitor mode. Make sure that there will be no problem with the actual system before using them. Connection methods for CPM2C CPM2C only has a connector with the same shape of the CS-Series’ peripheral port, but the signal cables inside are classified as used for the RS-232C port built in the CPU Unit and for the peripheral port.
Therefore, when using CPM2C, differentiate between the settings for the RS-232C port built in the CPU and for the peripheral port based on the conversion cable and port employed to ensure correct use. Besides, when using a simple communication device (CPM2C-CIF21 type), connect to the RS- 232C port. For details, refer to the CPM2C Operation Manual (W356). Use a self-made connection cable to connect the NB Unit and CPM2C. Connect to CPM2C’s built-in RS-232C port instead of the peripheral port. CS1W-CN118 type CPM2C RS-232C port (D-Sub 9-pin socket) When using a simple communication device (CPM2C-CIF21 type), connect to the RS-232C port directly.
RS-232C port NB-series Programmable Terminals Setup Manual(V107) 2-15 Host Model Channel No. Write Value Setting Port A of C200HX/HG/HE (-Z) (*1) DM6555 0001 Use Host Link DM6556 03(*3) Communication conditions are standard settings. (*4) DM6558 0000 Unit No. 00 Port 2 of CQM1H (*2) DM6550 0001 Use Host Link DM6551 03(*3) Communication conditions are standard settings. (*4) DM6553 0000 Unit No. 00 2 Port connected to the PT PLC System Settings CS1W-CN118 type port(D-Sub 9-pin) Carry out settings for the built-in RS-232C port