2 Installing the NB Unit and Connecting Peripheral Devices 2-5 UDP Communication Connection Connecting to a CJ-series CPU Unit Note 1 Always turn OFF the power to the PLC before setting the rotary switches. 2 Create I/O tables for the CPU Unit when setting the unit number for the first time or changing settings. CJ-series CPU Unit (Built-in EtherNet/IP Port): CJ2H-CPU -EIP CJ2M-CPU3 Setting Local IP Addresses Set the local IP address with the CX-Programmer or other Support Software. Refer to the SYSMAC CS/CJ Series Ethernet/IP Units Operation Manual (Cat. No. W465) for details on setting methods.
Setting the Front Panel Switches 2-5-4 Host Types and Settings of Ethernet/IP Unit Setting the Unit Numbers Set a unique unit number for the CJ2 CPU Unit built-in Ethernet/IP port. The same unit number cannot be used by any other CPU Bus Unit connected to the CJ2 CPU Unit. Use a small screwdriver to make the setting, and be sure not to damage the rotary switch. The unit number is factory-set to 0. UNIT No. Setting range 0 to F Setting Node Numbers Set a node address for the built-in Ethernet/IP port.
With the OMRON CJ/CS/NJ/CP UDP drive communications service, multiple Ethernet/IP Units (including the CJ2 Unit built-in Ethernet/IP port) connected by Ethernet are identified by their node addresses. Using the node address switches, set a unique node address in hexadecimal. The same node address cannot be used by any other Ethernet/IP Unit or Ethernet Unit connected on the same Ethernet network. As long as it does not duplicate any other address, the node address can be set from 01 to FE (1 to 254 in decimal). NODE No. Ч16 0 Ч16 1 Setting range 01 to FE hex (1 to 254 decimal) Note The node address is factory-set to 01.
With the default setting, the values set on these switches become the last two digits of the built-in Ethernet/IP port’s IP address. The default IP address is 192.168.250.node_address. With the factory-set node address of 01, the default IP address is 192.168.250.1. The Node ID of the rotary switch here must be consistent with that of PLC in the “Communication Setting” dialog box for the actual project created in the NB-Designer. NB-series Programmable Terminals Setup Manual(V107) 2-39 2