Nucleo GX Manual Page 87 Configuration Item Default Description Monitor for grid failure Disabled Monitors for loss of AC-input and triggers an alarm if detected. Alarm is cleared when the AC-input is reconnected. Settings → System Setup → ESS - Read full feature description. Mode Optimized with BatteryLife Options: Optimized with BatteryLife, Optimized without BatteryLife, Keep batteries charged, External control Grid metering Inverter/charger Leave this setting at Inverter/charger if no external grid meter is used. Set to External meter when using a supported external energy meter. Grid meter required Yes This option becomes available when Grid metering is set to External meter.
Sets the response when the external grid meter is lost. • With the setting "Yes", a grid meter must be present for ESS operation. If the meter is lost, the system switches to pass-through. • With the setting "No", the system will use a grid meter when present, but fall back to internal measurements if the connection to the grid meter is lost. Self-consumption from battery All system loads This setting allows for ESS to only use battery power for essential loads. Options are 'All system loads' or 'Only critical loads'. Multiphase regulation Total of all phases Use this setting in three-phase grid-connected systems. It enables phase compensation to help balance power flow across all phases.
Minimum SOC (unless grid fails) 10% Configurable minimum SoC limit. ESS will supply loads from the grid once the SoC has fallen to the configured setting - except when the utility grid has failed and the system is in Inverter mode. Active SOC limit 10% Use this setting to see the current BatteryLife SoC level. Only in 'Optimized with BatteryLife' mode. BatteryLife state Self-Consumption Displays the BatteryLife state, which can be one of the following: Self-consumption, Discharge disabled, Slow charge, Sustain, or Recharge. Only in 'Optimized with BatteryLife' mode. Limit inverter power Disabled Limit the power drawn by the Multi: ie. limit the power being inverted from DC to AC.
Grid set point 50W Defines the target power flow to the grid. A higher setpoint provides a buffer to help prevent unintentional energy export during sudden load changes. Grid feed-in Configure and limit the amount of power fed into the grid. Options include: AC-coupled PV - feed in excess, DC-coupled PV - feed in excess, Limit system feed-in. Also displays whether feed-in limiting is currently active. Peak shaving Above minimum SoC only Above minimum SoC only, or Always. Also includes a submenu to manually set the system AC import and export current limits per phase.
Scheduled charge levels Inactive Allows configuration of up to five time periods during which the system will charge the battery using power from the grid. Settings → System Setup → Batteries Battery monitor Automatic Select the SoC source. This function is useful where there is more than one source of battery. Options: Automatic, No battery monitor and available battery monitor sources. For more details see Battery state of charge (SoC) [92]. Auto-selected Displays the automatically selected SoC source when the ‘Battery monitor’ is set to ‘Automatic’. [Battery] Provides live data and a quick link to the individual battery page. Only available if Battery measurement is set to visible.
Battery measurements Use this menu to define the battery data shown when clicking the Battery icon on the Overview page. The same selection is also visible on the VRM Porta. Settings → System Setup → Charge Control - Read full feature description [105]