Nucleo GX Manual Page 89 Configuration Item Default Description State Not running Shows the state of the generator. Possible state messages: Stopped, Warm-up, Manually started, Running by condition, Cool- down, Stopping Error #0 No error Displays if there is an error (e.g. generator is supposed to be running but no AC input is detected) Settings Contains submenus for further configuration, such as Conditions, Warm-up & Cool-down, and Quiet Hours. Also includes a switch to enable an alarm if the generator is not in Autostart mode. Run time and service Displays the total generator runtime, daily runtime, time remaining until the next service, and the configured service interval.
Includes options to reset both the service timer and the daily runtime counter. Settings → Devices → Genset → Settings → Conditions On loss of communication Stop generator Defines what the system should do if communication with the GX device is lost. Options: Stop generator, Start generator, Keep generator running. Stop generator when AC input is available Disabled Useful for backup systems where a Quattro is connected to mains on one AC input and a generator on the other. When enabled, the generator will stop automatically once mains power becomes available again. Battery SOC Disabled Use the battery state of charge (SoC) to control generator start and stop behaviour. Enable to activate.
Start when SoC is lower than the defined percentage. A separate start value can be set for quiet hours to override them if necessary. Start after the SOC condition is reached for [seconds]. Stop when SoC is higher than the defined percentage. A separate stop value for quiet hours can be set to minimise runtime once the system has stabilised. A separate stop value can be set for quiet hours to override them if necessary. Battery current Battery voltage AC load Disabled Use any of the parameters to control generator start and stop behaviour. Enable to activate.
Start when value is higher than - Amps / Voltage / Watts Start value during quiet hours - Amps / Voltage / Watts (to override programmed quiet hours when absolutely necessary). Start after condition is reached for [seconds] (to allow for momentary spikes to pass without triggering start). Stop when value is lower than - Amps / Voltage / Watts. Stop value during quiet hours - Amps / Voltage / Watts (allows for less runtime during quiet hours, once system is recovered). Stop after the condition is reached for [seconds] (to allow for momentary dips without stopping the running generator).
Inverter high temperature Inverter overload Disabled Use inverter high temperature warning or inverter overload warning to control generator start and stop behaviour. Enable to activate. Start when warning is active for [seconds] (to allow for momentary spikes to pass without triggering start). When warning is cleared stop after [seconds] (to allow for momentary dips without stopping the running generator). On inverter overload warning it also allows to skip generator warm- up.