Nucleo GX Manual Page 90 Configuration Item Default Description Tank level Disabled Use the tank level to control generator start and stop behaviour. Enable to activate. Stop when Tank level is lower than threshold. Prevent start until Tank level is higher than threshold. Trigger warning when the generator is stopped. Periodic run Disabled Enable - No / Yes Run interval [days] Skip run if has been running for: Start always, 1, 2, 4, 6, 8, 10 hours. Run interval start [date] Start time [hh:mm] Run duration (hh:mm) Run until battery is fully charged. Default is disabled. Settings → Devices → Genset → Settings Conditions Submenu - see above.
Minimum run time 0m Defines a minimum run time in minutes. Detect generator at AC input Disabled When enabled, the system will trigger an alarm if no power from the generator is detected at the selected inverter AC input. Ensure that the correct AC input is assigned to “Generator” in the system setup. Alarm when generator is not in autostart mode Disabled When enabled, an alarm will trigger if the autostart function remains disabled for more than 10 minutes. Quiet hours Disabled Quiet hours will prevent normal generator run conditions from starting the generator.
It is possible for some settings to specify override values to the quiet hours (an extremely low battery voltage trigger to prevent a system shutdown for example). Warm-up & cool-down Warm-up time 60 Sets the delay time for generator warm-up via relay control before it is connected to the system. During this time, the AC input relay remains open and the inverter/charger is not yet connected. Cool-down time 180 Sets the delay time after the generator is disconnected from the system, allowing it to cool down before shutting off. The AC input relay remains open during this period.
Generator stop time 0 Settings → Devices → Genset → Run time and service Generator total run time (hours) Hours Displays the total number of hours the generator has operated. Daily run time Submenu displaying the daily run time for the last 30 days. Reset daily run time counters Provides an option to reset the generator’s run time counters. This is useful after generator replacement, major repairs, or when the counters are used for service tracking. Runtime until service Hours Displays the remaining run time before the next scheduled service. Enter the desired service interval in hours. Generator service interval Hours Sets the generator service interval in hours.
Determines how often maintenance is required based on run time. If not set, the Runtime until service item is hidden. Reset service timer Press to reset the service timer after the service is complete. Settings → Devices → Tank pump - Configure automatic pump start/stop based on tank level (sender) information. Pump state - Indicates whether the pump is currently running or stopped. Mode Auto Defines the pump control mode. Options are Auto, On, and Off. This acts as a manual override when a tank sensor is connected and start/ stop levels are defined. Tank Sensor No tank sensor Select the tank sensor used to trigger the pump.
If no sensor is connected or detected, “No tank sensor” will be shown.