Orion-Tr Smart DC-DC Charger Non-Isolated 7.1.2. Battery supply check Check that battery voltage is present at the charger's terminals. Measure the battery voltage at the charger battery terminals with a multimeter. V V The reason for measuring the battery voltage at the charger terminals is to rule out possible problems with the wiring, fuses and/or circuit breakers in the path between the battery and the charger. The charger is powered from the input side; without input voltage the charger stays off, even if the output battery is connected. Depending on the result of the measurement, do the following:
Page 16 Troubleshooting & Support Battery voltage Operational state Action to take No voltage Off Restore the battery supply. Check the external fuses, and check the wiring for loose or damaged cables and bad crimps. Pull-test the connections. Correct voltage Off Check for reverse battery polarity; see Reverse battery polarity [17]. If the polarity is correct, there might be a fault with the charger. Contact your Victron dealer or distributor. Correct voltage On Check for active errors via the VictronConnect app.