Delta Electronics — 3.12.1 Functions of Special Registers for Manual Mode Settings

3 Functions of Devices in DVP-PM Speed (PPS) Away from DOG signal DOG signal detected V CR V CR Zero return direction Number of pulses (P) in zero return Number of P 0 signals (N) in zero return G DOG DOG signal falling-edge triggered y b[9:10] = 01: normal mode; DOG signal rising-edge triggered 1. Zero return: The motor operates at zero return speed V RT . When it encounters DOG signal, it will decelerate to specified PG0 signals (N) plus the specified pulse signals (P). After both N signal and P pulses are finished, the zero return deceleration speed V CR . At the same time, rising edge of DOG signal is triggered to enable the motor stops. 2.

If the specified N or P is too small, when the rising edge of DOG signal is triggered, the motor will stop immediately after the specified PG0 signals (N) plus the specified pulse signals (P), even if the zero return deceleration speed (V CR ) is not yet reached. 3. If N and P are both set as “0”, the motor will stop immediately when the rising-edge of DOG signal is triggered. Speed (PPS) Away from DOG signal DOG signal detected Zero return direction V CR V CR Number of pulses (P) in zero return Number of P 0 signals (N) in zero return G DOG DOG signal rising -edge triggered y b[9:10] = 10: overwrite mode; DOG signal falling-edge triggered 1. Zero return:

The motor operates at zero return speed V RT . When it encounters DOG signal, it will decelerate to DVP-PM Application Manual 3-62