5 Categories and Use of Basic Application Instructions API 30 Operands: D : Device to be rotated n : Number of bits to be rotated in 1 rotation Explanations: 1. This instruction rotates bit status of the device D to the right for n bits 2. The status of the last bit rotated (marked with ※ ) is copied to the carry flag M1970 (Carry flag) 3. This instruction is generally used in pulse execution mode (RORP, DRORP). 4. When ROR is used as 16-bit instruction, Z device cannot be adopted; when ROR is used as 32-bit instruction, V device cannot be adopted. 5. When specifying the bit device of KnX(Y/M/S), the starting No. should be a multiple of 16 in octal or decimal format.
For example, K1X0, K4Y20 (octal); K1M0, K4S16 (decimal). 6. If operand D is specified as KnY, KnM or KnS, only K4 (16-bit) or K8 (32-bit) is valid. 7. Valid range of operand n : 1≤ n ≤16 (16-bit), 1≤ n ≤32 (32-bit) Program Example: When X0 goes from OFF to ON, the 16 bits (4 bits as a group) in D10 will rotate to the right, as shown in the figure below. The bit marked with ※ will be sent to carry flag M1970..
X0 Rotate to the right Upper bit Lower bit D10 M1022 Carry flag 16 bits After one rotation to the right D10 M1022 M1022 Upper bit lower bit 0 Carry flag * DVP-PM Operation Instruction 5-48 Mnemonic Operands Function Controllers 20PM 10PM D ROR P Rotation Right Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ROR, RORP: 5 steps DROR, DRORP: 9 steps D * * * * * * * * n * * RORP D10 K4 0 1 1 1 1 0 1 1 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 1 1 0 1 1 0 1 0 0