5 Categories and Use of Basic Application Instructions Operands: D : Device to be rotated n : Number of bits to be rotated in 1 rotation Explanation: 1. This instruction rotates bit status of the device D to the left for n bits 2. The status of the last bit rotated (marked with ※ ) is copied to the carry flag M1970. 3. This instruction is generally used in pulse execution mode (ROLP, DROLP). 4. When BMOV is used as 16-bit instruction, Z device cannot be adopted; when BMOV is used as 32-bit instruction, V device cannot be adopted. 5. When specifying the bit device of KnX(Y/M/S), the starting No. should be a multiple of 16 in octal or decimal format.
For example, K1X0, K4Y20 (octal); K1M0, K4S16 (decimal). 6. If operand D is specified as KnY, KnM or KnS, only K4 (16-bit) or K8 (32-bit) is valid. 7. Valid range of operand n : 1≤ n ≤16 (16-bit), 1≤ n ≤32 (32-bit) Program Example: When X0 goes from OFF to ON, all the 16 bits (4 bits as a group) in D10 will rotate to the left, as shown in the figure below. The bit marked with ※ will be sent to carry flag M1970.
X0 Upper bit Lower bit Rotate to the left M1022 D10 Carry flag After one rotation to the left 16 bits Upper bit Lower bit M1022 Carry flag 1 D10 DVP-PM Application Manual 5-49 API Mnemonic Operands Function Controllers 20PM 10PM 31 D ROL P Rotate Left Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ROL, ROLP: 5 steps DROL, DROLP: 9 steps D * * * * * * * * n * * ROLP D10 K4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1