Mitsubishi — 9.2.3.2 Start / Stop Acyclic E-CAM

9 Electrical CAM Reset by system Slave Position n n+60 n+300 T4 T7 Reset by system Master position D1846 b14=ON enables acyclic E-CAM M1812=ON, initialization completed Set by system Set by user T5 > 5ms E-CAM start signal PG0 / Start0 ( ) CLR0 sync output M1813, E-CAM completion T1 Reset by user „ Stop Acyclic E-CAM T2 T3 T6 There are two ways to stop acyclic E-CAM: 1. When D1846 bit 14 (enabling acyclic E-CAM) = OFF, Slave of E-CAM stops immediately. Slave Position n n+60 n+300 Master position D1846 b14=ON enables acyclic E-CAM M1812=ON, initialization completed Start signal of E-CAM ( / ) Pg0 Start0 Sync output M1813, E-CAM completion 2.

When M1748 (indicate E-CAM completion) is ON during E-CAM execution, Slave of E-CAM will stop until the current E-CAM cycle is completed n n+60 n+300 Slave Position Master position D1846 b14=ON enables acyclic E-CAM M1812=ON, initialization completed Start signal of E-CAM ( / ) Pg0 Start0 Sync output M1748, indicate E-CAM completion Set by user M1813, E-CAM completion Reset by user DVP-PM Application Manual 9-14