Mitsubishi — 13.5 Explanations on Control Registers

13 CANopen Communication Card CR#001 : Firmware version of DVP-FPMC [Explanantions] The firmware version of DVP-FPMC is displayed in hex values, e.g. H’8161 indicates the firware version issue date as “Afternoon, August 16.” CR#052 : CANopen synchronous packet sending setting [Explanantions] y Low Byte of CR052 sets up the CANopen synchronous function. When the value of the low byte is 1, DVP-FPMC will send out synchronous packet. If the value is 0, the function will be disabled. y High Byte of CR052 sets up the synchronous cycle time with DVP-PM. Care should be taken on setting the high-byte value. 5 times of the set value should equal to the value in D1040 of DVP-PM.

Synchronization between DVP-PM and DVP-FPMC will be enabled when the high-byte value is bigger than 1. CR#053 : DVP-FPMC CANopen node ID setting [Explanations] Set up the CANopen node ID within the range 5~127. Default: 127. CR#054 : DVP-FPMC CANopen transmission speed setting [Explanations] Set up the CANopen transmission speed. The setting status is indicated by b15; b15=1 indicates that setting is under progress and b15=0 indicates that setting is completed. For example, specify K1000 in CR#054 directly and the CANopen transmission speed will be set up as 1000kb/s. CR#055 : CANopen SDO / NMT timeout waiting time [Explanations] Set up the waiting time for CANopen SDO / NMT timeout. Unit:

ms. Default: 1000. CR#056 : DVP-FPMC error status [Explanations] Display the error status of DVP-FPMC. Please refer to the below table for the error status and the actions. DVP-PM Application Manual 13-6 Bit b15~ b8 B7~b0 Function Synchronous cycle time setting Enable synchronous packet sending Bit b15 b14~b0 Function Setting status 0: completed 1: under progress 1000: CANopen speed = 1000kb/s 500: CANopen speed = 500kb/s