13 CANopen Communication Card [Explanations] Set up the node ID of the SDO server within the range 1~127. CR#071 : SDO access command and status [Explanations] Set up the SDO access commands and obtain the status. Please refer to the table below for the setting format. SDO data transmission diagram: 1. Specify the OD index of SDO server (CR#070) in CR#072. 2. Set up the data to be transmitted in CR#073~CR#076. 3. Refer to the above table. Specify the subindex in b15~b8 of CR#071 and the SDO access commands as well. 1 OD index 2 3 CR#072 : SDO OD(Object Dictionary) index [Explanations] Specify the target OD index. Range: H’0000~H’FFFF. CR#073~CR#076 :
SDO OD sending/receiving data 1~4 [Explanations] The 4 registers store the data to be accessed (max 1024 bytes) through SDO protocol. When an error occurs DVP-PM Application Manual 13-8 Bit b15~b8 b7~b4 b3 b2~b0 Function Subindex of the the target OD index. Data length (unit: byte) Range: 1~8 Length of data should be specified in write-in cases Error flag Commands: 0: completed 1: write in (check up ) 2: read out (check up) 3: write in (No check up) 4: read out (No check up) Subindex Data Subindex Data Subindex Data Subindex Data Subindex Data Subindex Data