3 Functions of Devices in DVP-PM 32-bit High Speed Counter: „ 20PM: C200, C204 1. The setup range of 32-bit high speed counter: K-2,147,483,648 ~ K2,147,483,647. 2. C200/C204 counting mode setting: Note: z U/D: Counting up / Counting down, P/D: Pulse / Direction, A/B: A-phase / B-phase 3. M1908: Input signal control of C200 / C204 When M1908 = OFF, the input signal of C200 is controlled by MPG A0/B0 and reset signal is controlled by PG0. In addition, Input signal of C204 is controlled by MPG A1/B1 and reset signal is controlled by PG1.
Input pulse Pulse U A MPGA0 PV of C200 Dir C200 MPGB0 Input pulse D M1200/M1201 B Counting mode selection C200 reset signal M1203=1, PG0 Input pulse Pulse U A MPGA1 PV of C204 Dir C204 MPGB1 Input pulse D M1204/M1205 B Counting mode selection M1207=1, PG1 C204 reset signal When M1908 = ON, the 3 axes X/Y/Z share the same high speed counter C200. The input signal of C200 is controlled by MPG A0/B0. C200 reset signal is controlled by PG0. DVP-PM Application Manual 3-12 Counter Counting mode Reset signal (Valid only when b3 = 1) Input signal Device b0 / b1 1st set C200 K1M1200 0: U/D* 1: P/D* 2:
A/B* (Single frequency) 3:4A/B (Quadruple frequency) PG0 (M1203) A0+, A0-, B0+, B0- 2nd set C204 K1M1204 X11- (M1207) X2, X3, S/S