Mitsubishi — 3.7 Numbering and Functions of Counters [C]

3 Functions of Devices in DVP-PM Input pulse Pulse MPGA0 U A PV of C200 Dir C200 MPGB0 Input pulse D B M1200/M1201 Counting mode selection C200 reset signal M1203=1, PG0 4. SV can be K value (decimal) or D register (Special data register D1000~D2999 is not included). SV can be a positive or negative value. If a D register is specified as SV, it will occupy 2 consecutive data registers. 5. PV in the general purpose counter will be cleared when power of DVP-PM is OFF. If the counter is a latched (accumulative) type, PV and the contact status will be retained, and PLC will resume counting after power is ON again. 6. When PV reaches up to 2,147,483,647, the next PV will turn to -2,147,483,648.

When PV reaches down to -2,147,483,648, the next PV will turn to 2,147,483,647. „ 10PM: C200, C204, C208, C216, C220 1. The setup range of 32-bit high speed counter: K-2,147,483,648 ~ K2,147,483,647. 2. C200/C204/C208/C216/C220 counting mode settings: Note: z U/D: Counting up / Counting down, P/D: Pulse / Direction, A/B: A-phase / B-phase 3. Operation diagram: z Counting mode of C200 is selected by M1200/M1201. Input signal of C200 is controlled by X0/X1. Reset signal of C200 is enabled by M1203 and triggered by X10. DVP-PM Application Manual 3-13 Counter Counting mode Reset signal Reset terminal Input signal Device b0 / b1 1st set C200 K1M1200 0: U/D* 1: P/D* 2:

A/B* (Single frequency) 3:4A/B (Quadruple frequency) M1203 X10 X0, X1, S/S 2nd set C204 K1M1204 M1207 X11 X2, X3, S/S 3rd set C208 K1M1208 M1211 X12 X4, X5, S/S 4th set C212 K1M1212 M1215 X13 X6, X7, S/S 5th set C216 K1M1216 M1219 X0 X10+, X10-, X11+, X11- 6th set C220 K1M1220 M1223 X1 X12+, X12-, X13+, X13-